![background image](http://html1.mh-extra.com/html/danfoss/vacon-nx/vacon-nx_application-manual_3446098281.webp)
Selection number Function
Description
3
AI1–AI2
-
4
AI2–AI1
-
5
AI1*AI2
-
6
AI1 joystick
-
7
AI2 joystick
-
8
Keypad reference (R3.2)
-
9
Fieldbus reference
-
10
Potentiometer reference; controlled with ID 418 (TRUE=increase) and ID 417 (TRUE=de-
crease).
-
11
AI1 or AI2, whichever is lower.
-
12
AI1 or AI2, whichever is greater.
-
13
Max. frequency ID 102 (recommended in torque control only)
-
14
AI1/AI2 selection
See ID 422.
15
Encoder 1 (AI input C.1)
-
16
Encoder 2 (With OPTA7 Speed Synchronization, VACON
®
NXP only AI input C.3)
-
17
Master Reference
-
18
Master Ramp Out (default)
-
10.446 (ID 1082) SystemBus Communication Fault Response
Location in the menu:
P2.7.30
(Multi-purpose Control Application)
Use this parameter to select the response of the drive to an 'SystemBus communication'.
10.447 (ID 1083) Follower Torque Reference Selection
Location in the menu:
P2.11.4
(Multi-purpose Control Application)
Use this parameter to select the torque reference for the follower drive.
10.448 (ID 1084) Control Options
Location in the menu:
P2.4.19
(Multi-purpose Control Application)
Use this parameter to select the control option.
The parameter is available for VACON
®
NXP drives only.
Selection number
Selection name
b0
Disables encoder fault
b1
Update Ramp Generator when MotorControlMode changes from TC (4) to SC (3)
b2
RampUp; use acceleration ramp (for Closed Loop torque control)
b3
RampDown; use deceleration ramp (for Closed Loop torque control)
b4
FollowActual; follow actual speed value within WindowPos/ NegWidth (for closed loop torque control).
b5
TC ForceRampStop; Under stop request, the speed limit forces the motor to stop.
AB296635287482en-000301 / DPD00903 | 281
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......