Index
Parameter
Min
Max
Unit Default
ID
Description
P2.1.17
Wake up level
0.00
100.00 %
25.00
1018 -
P2.1.18
Wake up function
0
1
-
0
1019 0 = Wake-up at fall below
wake-up level (P2.1.17)
1 = Wake-up at exceeded
wake-up level (P2.1.17)
P2.1.19
Jogging speed reference
0.00
P2.1.2
Hz
10.00
124
-
1
Parameter value can only be changed after the AC drive has been stopped.
6.4.3 Input Signals (Control Panel: Menu M2 -> G2.2)
Table 37: Input Signals, G2.2
Index
Parameter
Min
Max
Unit Default ID
Description
P2.2.1
(1)
DIN 2 function
0
13
-
1
319
0 = Not used
1 = External fault cc
2 = External fault oc
3 = Run enable
4 = Acc/Dec time selection
5 = CP: I/O terminal (ID125)
6 = CP: Keypad (ID125)
7 = CP: Fieldbus (ID125)
8 = Forward/ Reverse
9 = Jogging frequency (cc)
10 = Fault reset (cc)
11 = Acc/Dec prohibit (cc)
12 = DC braking command
13 = Motor pot. UP (cc)
P2.2.2
(1)
DIN 3 function
0
13
-
10
301
See P2.2.1 except:
13 = Motor pot. DOWN (cc)
P2.2.3
(1)
DIN 5 function
0
13
-
9
330
See P2.2.1 except:
13 = Enable PID reference 2
P2.2.4
(1)
PID sum point reference 0
7
-
0
376
0 = Direct PID output value
1 = AI1+PID output
2 = AI2+PID output
3 = AI3+PID output
4 = AI4+PID output
5 = PID PID output
6 = FPID output (Process- DataIN3)
7 = Mot.pot.+PID output
P2.2.5
(1)
I/O B reference selec-
tion
0
7
-
1
343
0 = AI1 1 = AI2
2 = AI3
3 = AI4
4 = Keypad reference
5 = Fieldbus reference (FBSpeedReference)
P2.2.6
(1)
Keypad control refer-
ence selection
0
7
-
4
121
AB296635287482en-000301 / DPD00903 | 65
Danfoss A/S © 2023.02
PID Control Application
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......