Table 116: Selections for Parameter ID 301
Selection
number
Selection name
Description
Notes
0
Not used
-
-
1
External fault
Closing contact: Fault is shown and
responded to according to ID 701.
-
2
External fault
Opening contact: Fault is shown and
responded to according to ID 701
when the input is not active.
-
3
Run enable
Contact open: Motor start disabled
and the motor is stopped READY sig-
nal is set to FALSE
Contact closed: Motor start enabled
-
Basic Application
4
Run enable
Contact open: Motor start enabled
Contact closed: Motor start disabled
and the motor is stopped
-
Standard Application, Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID
Control Application
4
Acc./Dec time se-
lect.
Contact open: Acceleration/decelera-
tion time 1 selected
Contact closed: Acceleration/deceler-
ation time 2 selected
When the control place is forced to change, the
values of Start/Stop, Direction, and Reference
valid in the respective control place are used
(reference according to parameters ID 117, ID
121, and ID 122).
The value of parameter ID 125 Keypad Control
Place does not change. When DIN 3 opens, the
control place is selected according to parame-
ter 3.1.
5
Closing contact
Force control place to I/O terminal
6
Closing contact
Force control place to keypad
7
Closing contact
Force control place to fieldbus
8
Reverse
Contact open: Forward
Contact closed: Reverse
Can be used for reversing if parameter ID300
value is set to either 2, 3, or 6.
Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application
9
Jogging sp.
Contact closed: Jogging speed selec-
ted for frequency reference
-
10
Fault reset
Contact closed: Resets all faults
-
11
Acc./dec. operation
prohibited
Contact closed: Stops acceleration or
deceleration until the contact is
opened
-
12
DC-braking com-
mand
Contact closed: In Stop mode, the DC-
braking operates until the contact is
opened, see Figure 30 and parame-
ters ID 507 and ID 1080
-
Local/Remote Control Application, PID Control Application
AB296635287482en-000301 / DPD00903
184 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide