B
Maximum value of signal selected with ID 307
Maximum output signal = Minimum set value
Minimum output signal = Maximum set value
See
10.71 (ID 311) Analog Output 1 Scale
10.70 (ID 310) Analog Output 1 Minimum
Location in the menu:
P2.3.5
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application)
P2.3.5.5
(Multi-Purpose Control Application)
P2.3.3.5
(Pump and Fan Control Application)
Use this parameter to set the minimum value of the analog output 1 signal.
The parameter defines the signal minimum to either 0 mA or 4 mA (living zero). Note the difference in analog output scaling in
parameter
ID 311
.
10.71 (ID 311) Analog Output 1 Scale
Location in the menu:
P2.3.6
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Application)
P2.3.5.6
(Multi-Purpose Control Application)
P2.3.3.6
(Pump and Fan Control Application)
Use this parameter to set the scaling factor for the analog 1 output.
Signal
Max. value of the signal
Output frequency
Max frequency (parameter ID102)
Freq. Reference
Max frequency (parameter ID102)
Motor speed
Motor nom. speed 1xn
mMotor
Output current
Motor nom. current 1xI
nMotor
Motor torque
Motor nom. torque 1xT
nMotor
Motor power
Motor nom. power 1xP
nMotor
Motor voltage
100% x U
nmotor
DC-link voltage
1000 V
PI-ref. value
100% x ref. value maximum
PI act. value 1
100% x actual value maximum
PI act. value 2
100% x actual value maximum
PI error value
100% x error value maximum
PI output
100% x output maximum
AB296635287482en-000301 / DPD00903 | 189
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide