P2.3.1.29
(1)
Autochange 3/Aux 3 control
0.1
0.1
460
-
P2.3.1.30
(1)
Autochange 4/Aux 4 control
0.1
0.1
461
-
P2.3.1.31
(1)
Autochange 5
0.1
0.1
461
-
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
)
Table 99: Limit Settings (Control Panel: Menu M2 -> G2.3.2)
Index
Parameter
Min
Max
Unit Default ID
Description
P2.3.2.1
Output frequency limit 1 supervision
0
2
-
0
315 0 = No supervision
1 = Low limit supervision
2 = High limit supervision
P2.3.2.2
Output frequency limit 1; Supervised value
0.00
320.00 Hz
0.00
316 -
P2.3.2.3
Output frequency limit 2 supervision
0
2
0
346 0 = No limit
1 = Low limit supervision
2 = High limit supervision
P2.3.2.4
Output frequency limit 2; Supervised value
0.00
320.00 Hz
0.00
347 -
P2.3.2.5
Torque limit supervision
0
2
-
0
348 0 = Not used
1 = Low limit supervision
2 = High limit supervision
P2.3.2.6
Torque limit supervision value
-300.0 300.0
%
100.0
349 -
P2.3.2.7
Reference limit supervision
0
2
-
0
350 0 = No supervision
1 = Low limit
2 = High limit
P2.3.2.8
Reference limit supervision value
0.0
100.0
%
0.0
351 -
P2.3.2.9
External brake-off delay
0.0
100.0
s
0.5
352 -
P2.3.2.10 External brake-on delay
0.0
100.0
s
1.5
353 -
P2.3.2.11 Frequency converter temperature supervision
0
2
-
0
354 0 = No supervision
1 = Low limit
2 = High limit
P2.3.2.12 Frequency converter temperature supervised
value
-10
100
°C
40
355 -
P2.3.2.13 Supervised analog input
0
1
-
0
372 0 = AI1
1 = AI2
P2.3.2.14 Analog input limit supervision
0
2
-
0
373 0 = No limit
1 = Low limit supervision
AB296635287482en-000301 / DPD00903 | 141
Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide