Index
Parameter
Min
Max
Unit
Default
ID
Description
1 = Inverted
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
2
Remember to place jumpers of block X2 according to the selection (0, 1, 2 or 3). See the User Manual of the product.
Table 96: Analog Input 4 (Control Panel: Menu M2 -> G2.2.5)
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.5.1
(1)
AI4 signal selection
0.1
E.10
-
0.1
152
-
P2.2.5.2
AI4 filter time
0.00
10.00
s
0.00
153
0 = No filtering
P2.2.5.3
(2)
AI4 signal range
0
2
-
1
154
0 = 0–10 V (0–20 mA)
1 = 2–10 V (4–20 mA)
2 = Customised
P2.2.5.4
AI4 custom minimum setting
-160.00
160.00
%
0.00
155
-
P2.2.5.5
AI4 custom maximum setting
-160.00
160.00
%
100.00
156
-
P2.2.5.6
AI4 signal inversion
0
1
-
0
162
0 = Not inverted
1 = Inverted
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
2
Remember to place jumpers of block X2 according to the selection (0, 1, or 2). See the User Manual of the product.
Table 97: Digital Inputs (Control Panel: Menu M2 -> G2.2.4)
Index
Parameter
Min
Default
ID
Description
P2.2.6.1
(1)
Start A signal
0.1
A.1
423
-
P2.2.6.2
(1)
Start B signal
0.1
A.4
424
-
P2.2.6.3
(1)
Control place A/B selection
0.1
A.6
425
-
P2.2.6.4
(1)
External fault (cc)
0.1
0.1
405
-
P2.2.6.5
(1)
External fault (oc)
0.1
0.2
406
-
P2.2.6.6
(1)
Run enable
0.1
0.2
407
-
P2.2.6.7
(1)
Acc/Dec time selection
0.1
0.1
408
-
P2.2.6.8
(1)
Control from I/O terminal
0.1
0.1
409
-
P2.2.6.9
(1)
Control from keypad
0.1
0.1
410
-
P2.2.6.10
(1)
Control from fieldbus
0.1
0.1
411
-
P2.2.6.11
(1)
Reverse
0.1
0.1
412
-
AB296635287482en-000301 / DPD00903
138 | Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide