Selection
number
Selection name
Description
Notes
13
Motor potentiome-
ter down
Contact closed: Reference decreases
until the contact is opened
-
Multi-Step Speed Control Application
13
Preset speed
-
A
B
t
t
ID515
DIN3
f
out
f
out
RUN
STOP
DIN3
RUN
STOP
e
3
0
b
h
0
2
8
.1
0
Illustration 34: DIN 3 as DC brake Command Input
A
Stop mode = Ramp
B
Stop mode = coasting
10.62 (ID 302) Analog Input 2, Reference Offset
Location in the menu:
P2.15
(Basic Application)
P2.2.3
(Standard Application)
Use this parameter to set the reference offset for analog input.
Selection num-
ber
Selection name
Description
0
No offset: 0–20 mA
-
1
Offset 4 mA (“living zero”) Provides supervision of zero level signal. In Standard Application, the response
to reference fault can be programmed with parameter ID 700.
10.63 (ID 303) Reference Scaling, Minimum Value
Location in the menu:
P2.2.4
(Standard Application)
P2.2.16
(Local/Remote Control Application)
P2.2.15
(Multi-Step Speed Control Application
P2.2.2.6
(Multi-Purpose Control Application)
Use this parameter to set extra reference scaling.
See also
10.64 (ID 304) Reference Scaling, Maximum Value
10.64 (ID 304) Reference Scaling, Maximum Value
Location in the menu:
AB296635287482en-000301 / DPD00903 | 185
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide