7.4.2 Basic Parameters (Control Panel: Menu M2 -> G2.1)
Table 55: Basic Parameters G2.1
Index
Parameter
Min
Max
Unit Default
ID
Description
P2.1.1
Min frequency
0.00
P2.1.2
Hz
0.00
101 -
P2.1.2
Max frequency
P2.1.1
320.00
Hz
50.00
102 -
P2.1.3
Acceleration time 1
0.1
3000.0
s
3.0
103 -
P2.1.4
Deceleration time 1
0.1
3000.0
s
3.0
104 -
P2.1.5
Current limit
Varies Varies
A
0.00
107 -
P2.1.6
(1)
Nominal voltage of the motor
180
690
V
NX2: 230 V
NX5: 400 V
NX6: 690 V
110 -
P2.1.7
(1)
Nominal frequency of the motor
8.00
320.00
Hz
50.00
111 -
P2.1.8
(1)
Nominal speed of the motor
24
20 000
RPM 1440
112 -
P2.1.9
(1)
Nominal current of the motor
Varies Varies
A
5.40
113 -
P2.1.10
Motor cos phi
0.30
1.00
-
0.85
120 -
P2.1.11
I/O reference
0
15/16
-
0
117 0 = AI1
1 = AI2
2 = AI1+AI2
3 = AI1-AI2
4 = AI2-AI1
5 = AI1xAI2
6 = AI1 Joystick
7 = AI2 Joystick
8 = Keypad
9 = Fieldbus
10 = Motor potentiometer
11 = AI1, AI2 minimum
12 = AI1, AI2 maximum
13 = Max frequency
14 = AI1/AI2 selection
15 = Encoder 1
16 = Encoder 2 (VACON
®
NXP only)
P2.1.12
Keypad control reference
0
9
-
8
121 0 = AI1
1 = AI2
2 = AI1+AI2
3 = AI1-AI2
4 = AI2-AI1
5 = AI1xAI2
6 = AI1 Joystick
7 = AI2 Joystick
P2.1.13
Fieldbus control reference
0
9
-
9
122