The motor torque goes beyond the set supervision limits (see parameters
ID 348
and
ID 349
).
10.196 (ID 452) Thermistor Fault or Warning
Location in the menu:
P2.3.1.21
(Pump and Fan Control Application)
P2.3.3.21
(Multi-Purpose Control Application)
Use this parameter to select a digital output for the motor thermal fault status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Motor thermistor initiates an overtemperature signal which can be led to a digital output.
This function requires an AC drive equipped with a thermistor input.
10.197 (ID 453) Analog Input Supervision
Location in the menu:
P2.3.3.22
(Multi-Purpose Control Application)
Use this parameter to select a digital output for the analog input supervision status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
The selected analog input signal goes beyond the set supervision limits (see parameters ID 372, ID 373, and ID 374).
10.198 (ID 454) Motor Regulator Activation
Location in the menu:
P2.3.1.23
(Pump and Fan Control Application)
P2.3.3.23
(Multi-Purpose Control Application)
Use this parameter to select a digital output for the motor regulator status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
One of the limit regulators (current limit, torque limit) has been activated.
10.199 (ID 455) Fieldbus Digital Input 1
Location in the menu:
P2.3.1.24
(Pump and Fan Control Application)
P2.3.3.24
(Multi-Purpose Control Application)
Use this parameter to select a digital output for the FBFixedControlWord B3 status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
See the fieldbus manual for details. See also
ID 169
and
ID 170
.
10.200 (ID 456) Fieldbus Digital Input 2
Location in the menu:
P2.3.1.25
(Pump and Fan Control Application)
P2.3.3.25
(Multi-Purpose Control Application)
Use this parameter to select a digital output for the FBFixedControlWord B4 status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
See the fieldbus manual for details. See also
ID 169
and
ID 170
.
10.201 (ID 457) Fieldbus Digital Input 3
Location in the menu:
P2.3.1.26
(Pump and Fan Control Application)
P2.3.3.26
(Multi-Purpose Control Application)
Use this parameter to select a digital output for the FBFixedControlWord B5 status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
See the fieldbus manual for details. See also
ID 169
and
ID 170
.
AB296635287482en-000301 / DPD00903
224 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide