Index
Parameter
Min
Max
Unit
Default
ID
Description
1 = Inverted
P2.3.6.5
Analog output 2 minimum
0
1
-
0
475
0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.6.6
Analog output 2 scale
10
1000
%
100
476
-
P2.3.6.7
Analog output 2 offset
-100.00
100.00
%
0.00
477
-
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
.
Table 102: Analog Output 3 (Control Panel: Menu M2 -> G2.3.7)
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.3.5.1
(1)
Analog output 3 signal selection
0.1
E.10
-
0.1
478
-
P2.3.5.2
Analog output 3 function
0
14
-
4
479
See P2.3.3.2
P2.3.5.3
Analog output 3 filter time
0.00
10.00
s
1.00
480
0 = No filtering
P2.3.5.4
Analog output 3 inversion
0
1
-
0
481
0 = Not inverted
1 = Inverted
P2.3.5.5
Analog output 3 minimum
0
1
-
0
482
0 = 0 mA (0 V)
1 = 4 mA (2 V)
P2.3.5.6
Analog output 3 scale
10
1000
%
100
483
-
P2.3.5.7
Analog output 3 offset
-100.00
100.00
%
0.00
484
-
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
.
8.4.5 Drive Control Parameters (Control Panel: Menu M2 -> G2.4)
Table 103: Drive Control Parameters, G2.4
Index
Parameter
Min Max
Unit Default ID
Description
P2.4.1
Ramp 1 shape
0.0
10.0
s
0.1
500 0 = Linear
100 = full acc/dec inc/dec tmes
P2.4.2
Ramp 2 shape
0.0
10.0
s
0.0
501 0 = Linear
100 = full acc/dec inc/dec tmes
P2.4.3
Acceleration time 2
0.1
3000.0 s
1.0
502 -
P2.4.4
Deceleration time 2
0.1
3000.0 s
1.0
503 -
P2.4.5
Brake chopper
0
4
-
0
504 0 = Disabled
1 = Used when running
2 = External brake chopper
3 = Used when stopped/running
AB296635287482en-000301 / DPD00903 | 143
Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide