Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.19
Zero frequency load
5.0
150.0
%
10.0
715
-
P2.7.20
Underload protection time limit
2.00
600.00
s
20.00
716
-
P2.7.21
Response to thermistor fault
0
3
-
2
732
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.22
Response to fieldbus fault
0
3
-
2
733
P2.7.23
Response to slot fault
0
3
-
2
734
P2.7.24
TBoard1 Numbers
0
5
-
0
739
0 = Not used
1 = Channel 1
2 = Channel 1 & 2
3 = Channel 1 & 2 & 3
4 = Channel 2 & 3
5 = Channel 3
P2.7.25
TBoard Flt. Resp
0
3
-
0
740
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
P2.7.26
TBoard1 Warn.Lim
-30.0
200.0
ºC
120.0
741
-
P2.7.27
TBoard1 Flt.Lim
-30.0
200.0
ºC
130.0
742
-
P2.7.37
TBoard2 Numbers
0
5
-
0
743
0 = Not used
1 = Channel 1
2 = Channel 1 & 2
3 = Channel 1 & 2 & 3
4 = Channel 2 & 3
5 = Channel 3
P2.7.38
TBoard2 Warn.Lim
-30.0
200.0
Cº
120
745
-
P2.7.39
TBoard2 Flt.Lim
-30.0
200.0
Cº
130
746
-
Table 82: Protections, VACON
®
NXP, G2.7
Index
Parameter
Min
Max
Unit Default ID
Description
P2.7.1
Response to 4 mA reference
fault
0
5
-
0
700
0 = No response
1 = Warning
2 = Previous Freq.
3 = Wrng+Preset- Freq 2.7.2
4 = Fault, stop acc. to 2.4.7
5 = Fault, stop by coasting
P2.7.2
4 mA reference fault fre-
quency
0.00
P2.1.2
Hz
0.00
728
-
AB296635287482en-000301 / DPD00903
114 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......