Index
Parameter
Min Max
Unit Default ID
Description
Ctrl sgn 2 = Enable pulse
P2.2.1.2
(1)
Motor potentiometer
ramp time
0.1
2000.0 Hz/s 10.0
331
-
P2.2.1.3
(1)
Motor potentiometer
frequency reference
memory reset
0
2
-
1
367
0 = No reset
1 = Reset if stopped or powered down
2 = Reset if powered down
P2.2.1.4
(1)
Adjust input
0
5
-
0
493
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = Fieldbus (see group G2.9)
P2.2.1.5
Adjust minimum
0.0
100.0
%
0.0
494
-
P2.2.1.6
Adjust maximum
0.0
100.0
%
0.0
495
-
P2.2.1.7
Inversion control
1091 B00 = +1 = Invert External fault 1
B01 = +2 = Invert External fault 2
B06 = +64 = Invert Ambient Temperature Monitor
B07 = +128 = Invert Input Switch
B010 = +1024 = Invert Klixon 1
B011 = +2048 = Invert Klixon 2
1
Parameter value can only be changed after the AC drive has been stopped.
Table 57: Analog Input 1 (Control Panel: Menu M2 -> G2.2.2)
Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.2.2.1
(1)
AI1 signal selection
0.1
E.10
-
A.1
377
-
P2.2.2.2
AI1 filter time
0.00
320.00
s
0.10
324
P2.2.2.3
(2)
AI1 signal range
0
3
-
0
320
0 = 0–10 V (0–20 mA)
1 = 2–10 V (4–20 mA)
2 = -10V...+10 V
3 = Custom range
P2.2.2.4
AI1 custom minimum setting
-160.00
160.00
%
0.00
321
-
P2.2.2.5
AI1 custom maximum setting
-160.00
160.00
%
100.00
322
-
P2.2.2.6
AI1 reference scaling, minimum value
0.00
320.00
Hz
0.00
303
-
P2.2.2.7
AI1 reference scaling, maximum value
0.00
320.00
Hz
0.00
304
-
P2.2.2.8
AI1 joystick hysteresis
0.00
20.00
%
0.00
384
-
AB296635287482en-000301 / DPD00903 | 93
Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide