Index
Parameter
Min
Max
Unit
Default
ID
Description
P2.7.23
Response to slot fault
0
3
-
2
734
See P2.7.21
P2.7.24
No. of PT100 inputs
0
3
-
0
739
0 = Not used
1 = Channel 1
2 = Channel 1 & 2
3 = Channel 1 & 2 & 3
P2.7.25
Response to PT100 fault
0
3
-
0
740
0 = No response
1 = Warning
2 = Fault,stop acc. to 2.4.7
3 = Fault,stop by coasting
P2.7.26
PT100 warning limit
-30.0
200.0
ºC
120.0
741
-
P2.7.27
PT100 fault limit
-30.0
200.0
ºC
130.0
742
-
8.4.9 Auto Restart Parameters (Control Panel: Menu M2 -> G2.8)
Table 107: Auto Restart Parameters, G2.8
Index
Parameter
Min
Max
Unit Default
ID
Description
P2.8.1
Wait time
0.10 10.00
s
0.50
717 -
P2.8.2
Trial time
0.00 60.00
s
30.00
718 -
P2.8.3
Start function
0
2
-
0
719 0 = Ramp
1 = Flying start
2 = According to P2.4.6
P2.8.4
Number of tries after undervoltage trip
0
10
-
1
720 -
P2.8.5
Number of tries after overvoltage trip
0
10
-
1
721 -
P2.8.6
Number of tries after overcurrent trip
0
3
-
1
722 -
P2.8.7
Number of tries after 4 mA reference trip
0
10
-
1
723 -
P2.8.8
Number of tries after motor temperature fault trip
0
10
-
1
726 -
P2.8.9
Number of tries after external fault trip
0
10
-
0
725 -
P2.8.10
Number of tries after underload fault trip
0
10
-
1
738 -
AB296635287482en-000301 / DPD00903 | 147
Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide