Index
Parameter
Min
Max
Unit
Default
ID
Description
2 = Used (ramping)
P2.6.11
Undervoltage controller
0
2
-
2
608
0 = Not used
1 = Used
2 = Used (ramping to zero)
P2.6.12
Load drooping
0.00
100.00
%
0.00
620
-
P2.6.13
Identification
0
2/5
-
0
631
0 = No action
1 = Identification w/o run
2 = Identification with run
Only VACON
®
NXP:
3 = Encoder ID run
4 = No action
5 = ID Run Failed
Closed Loop parameter group 2.6.14
P2.6.14.1
Magnetizing current
0.00
2 x I
H
A
0.00
612
-
P2.6.14.2
Speed control P gain
1
1000
-
30
613
-
P2.6.14.3
Speed control I time
0.0
3200.0
ms
30.0
614
-
P2.6.14.5
Acceleration compensation
0.00
300.00
s
0.00
626
-
P2.6.14.6
Slip adjust
0
500
%
100
619
-
P2.6.14.7
Magnetizing current at start
0.00
I
L
A
0.00
627
-
P2.6.14.8
Magnetizing time at start
0
60000
ms
0
628
-
P2.6.14.9
0-speed time at start
0
32000
ms
100
615
-
P2.6.14.10
0-speed time at stop
0
32000
ms
100
616
-
P2.6.14.11
Start-up torque
0
3
-
0
621
0 = Not used
1 = Torque memory
2 = Torque reference
3 = Start-up torque fwd/rev
P2.6.14.12
Start-up torque FWD
-300.0
300.0
%
0.0
633
-
P2.6.14.13
Start-up torque REV
-300.0
300.0
%
0.0
634
-
P2.6.14.15
Encoder filter time
0.0
100
ms
0.0
618
-
AB296635287482en-000301 / DPD00903
56 | Danfoss A/S © 2023.02
Multi-step Speed Control
Application
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......