Index
Parameter
Min
Max
Unit Default ID
Description
P2.2.13
AI2 signal inversion
0
1
-
0
328 0 = Not inverted
1 = Inverted
P2.2.14
AI2 signal filter time
0.00
10.00
s
0.10
329 -
P2.2.15
(1)
Place B Start/Stop logic selection
0
6
-
0
363
Logic = 0
Ctrl sgn 1 = Start forward
Ctrl sgn 2 = Start reverse
Logic = 1
Ctrl sgn 1 = Start/ Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/ Stop
Ctrl sgn 2 = Run enable
Logic = 3
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Stop pulse
Logic = 4
Ctrl sgn 1 = Forward pulse (edge)
Ctrl sgn 2 = Reverse pulse (edge)
Logic = 5
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Reverse pulse
Logic = 6
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Enable pulse
P2.2.16
Place A Reference scaling mini-
mum value
0.00
320.00 Hz
0.00
303 -
P2.2.17
Place A Reference scaling maxi-
mum value
0.00
-
-
-
304 -
P2.2.18
Place B Reference scaling mini-
mum value
0.00
320.00 Hz
0.00
364 -
P2.2.19
Place B Reference scaling maxi-
mum value
0.00
320.00 Hz
0.00
365 0.00 = No scaling
>0 = scaled maximum value
P2.2.20
Free analog input, signal selec-
tion
0
2
-
0
361 0 = Not used
1 = Analog input 1
2= Analog input 2
P2.2.21
Free analog input, function
0
4
-
0
362 0 = No reset
1 = Reduces current limit (P2.1.5)
2 = Reduces DC braking current
3 = Reduces accel. and decel. times
4 = Reduces torque super vision limit
AB296635287482en-000301 / DPD00903
36 | Danfoss A/S © 2023.02
Local/Remote Control Application
VACON® NX All-in-One
Application Guide