Index
Parameter
Min Max Unit De-
fault
ID
Description
3 = Stop by ramping, deceleration ramp according to ramp
configured to the safety option board
P2.12.2 Response to SLS
request
0
3
-
0
543
P2.12.3 Response to SDI
request
0
1
-
0
544 0 = No action
1 = Prohibit speed reference on unintended direction
7.4.15 Condition-based Monitoring (Control Panel: Menu M2 -> G.13)
For more detailed information on the commissioning and use of Condition-based Monitoring, refer to the VACON
®
Condition-based
Monitoring Application Guide.
Table 88: Condition-based Monitoring Parameters, G2.13
Index
Name
Min
Max
Unit
Default
ID
Description
P2.13.1.1
Baseline Type
0
3
-
0
3501
0 = No Action
1 = Baseline Run
2 = Online Baseline
3 = Baseline Finished
P2.13.1.2
Baseline Min Freq
0.00
320.00
Hz
0
3502
-
P2.13.1.3
Baseline Max Freq
0.00
320.00
Hz
50.00
3503
-
P2.13.1.4
Baseline Duration
1
300 000
min
2
3504
-
P2.13.1.5
Modified Array
0
16
-
0
3506
0 = Freq Points
1 = Current Max Steady
2 = Current Min Steady
3 = Current Mean Steady
4 = Current Std Steady
5 = Voltage Max Steady
6 = Voltage Min Steady
7 = Voltage Mean Steady
8 = Voltage Std Steady
9 = Vibration Max Ramp
10= Vibration Min Ramp
11 = Vibration Mean Ramp
12 = Vibration Std Ramp
13 = Load Max Steady
14 = Load Min Steady
15 = Load Mean Steady
16 = Load Std Steady
P2.13.1.6
Modified Point
0
9
-
0
3507
-
P2.13.1.7
Modified Value
-300.00
320.00
Hz or %
0
3508
-
P2.13.1.8
Modified Activation
0
1
-
0
3505
-
P2.13.1.9
Baseline Data Selector
0
20
-
0
3509
0 = Freq Points
1 = Current Max Steady
2 = Current Min Steady
3 = Current Mean Steady
AB296635287482en-000301 / DPD00903 | 123
Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......