Index
Parameter
Min
Max
Unit Default ID
Description
P2.9.22 Frequency increase delay
0.0
300.0
s
0.0
1026 0 = No delay
300 = No frequency drop nor
increase
P2.9.23 Interlock selection
0
2
-
1
1032 0 = Interlocks not used
1 = Set new interlock last; up-
date order after value of
P2.9.26 or Stop state
2 = Stop and update order im-
mediately
P2.9.24 Autochange
0
1
-
1
1027 0 = Not used
1 = Autochange used
P2.9.25 Autoch. and interl. automatics selection
0
1
-
1
1028 0 = Auxiliary drives only
1 = All drives
P2.9.26 Autochange interval
0.0
3000.0 h
48.0
1029 0.0 = TEST=40 s
P2.9.27 Autochange; Maximum number of auxiliary
drives
0
4
-
1
1030 -
P2.9.28 Autochange frequency limit
0.00
P2.1.2
Hz
25.00
1031 -
P2.9.29 Actual value special display minimum
0
30000
-
0
1033 -
P2.9.30 Actual value special display maximum
0
30000
-
100
1034 -
P2.9.31 Actual value special display decimals
0
4
-
1
1035 -
P2.9.32 Actual value special display unit
0
28
-
4
1036 See
8.4.11 Keypad Control (Control Panel: Menu M3)
The parameters for the selection of control place and direction on the keypad are listed in the table. See the
Keypad control
menu in
the User Manual of the product.
Table 109: Keypad Control Parameters, M3
Index
Parameter
Min
Max
Unit
Default
ID
Description
P3.1
Control place
1
3
-
1
125
1 = I/0 terminal
2 = Keypad
3 = Fieldbus
P3.2
Keypad reference
P2.1.1
P2.1.2
Hz
0.00
-
-
P3.3
Direction (on keypad)
0
1
-
0
123
0 = Forward
1 = Reverse
AB296635287482en-000301 / DPD00903 | 149
Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide