Index
Parameter
Min
Max
Unit Default ID
Description
P2.2.17
AI1 custom minimum
setting
–160.00 160.00
%
0.00
321
-
P2.2.18
Free analog input, func-
tion
–160.00 160.00
%
100.0
322
-
P2.2.19
AI1 inversion
0
1
-
0
323
0 = Not inverted
1 = Inverted
P2.2.20
AI1 filter time
0.00
10.00
s
0.10
324
-
P2.2.21
(3)
AI2 signal selection
0.1
E.10
-
A.2
388
0 = 0–20 mA (0–10 V)
1 = 4–20 mA (2–10 V)
2 = Custom range
P2.2.22
(3)
AI2 signal range
0
2
-
1
325
0 = 0–20 mA
1 = 4–20 mA
2 = Customised
P2.2.23
AI2 custom minimum
setting
-160.00
160.00
%
0.00
326
-
P2.2.24
AI2 custom maximum
setting
-160.00
160.00
%
0.00
327
-
P2.2.25
AI2 inversion
0
1
-
0
328
0 = Not inverted
1 = Inverted
P2.2.26
AI2 filter time
0.00
10.00
s
0.10
329
0 = No filtering
P2.2.27
Motor potentiometer
ramp time
0.1
2000.0
Hz/s 10.0
331
-
P2.2.28
Motor potentiometer
frequency reference
memory reset
0
2
-
1
367
0 = No reset
1 = Reset if stopped or powered down
2 = Reset if powered down
P2.2.29
Motor potentiometer
PID reference memory
reset
0
2
-
0
370
P2.2.30
PID minimum limit
-1600.0
P2.2.31 %
0.0
359
-
P2.2.31
PID maximum limit
P2.2.30
1600.0
%
100.0
360
-
P2.2.32
Error value inversion
0
1
-
0
340
0 = No inversion
1 = Inversion
P2.2.33
PID reference rising
time
0.1
100.0
s
5.0
341
-
P2.2.34
PID reference falling
time
0.1
100.0
s
5.0
342
-
AB296635287482en-000301 / DPD00903 | 67
Danfoss A/S © 2023.02
PID Control Application
VACON® NX All-in-One
Application Guide
Содержание VACON NX
Страница 1: ...Application Guide VACON NX All in One drives danfoss com...
Страница 2: ......