P2.7.3
Response to external fault 1
0
3
-
2
701
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.4
Input phase supervision
0
3
-
3
730
P2.7.5
Response to undervoltage
fault
0
1
-
0
727
0 = Fault stored in history
1 = Fault not stored
P2.7.6
Output phase supervision
0
3
-
2
702
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.7
Earth fault protection
0
3
-
2
703
P2.7.8
Thermal protection of the
motor
0
3
-
2
704
P2.7.9
Motor ambient tempera-
ture factor
-100.0 100.0
%
0.0
705
-
P2.7.10
Motor cooling factor at zero
speed
0.0
150.0
%
40.0
706
-
P2.7.11
Motor thermal time con-
stant
1
200
min
Varies
707
-
P2.7.12
Motor duty cycle
0
150
%
100
708
-
P2.7.13
Stall protection
0
3
-
0
709
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.14
Stall current
0.00
P2.1.2
A
I
H
710
-
P2.7.15
Stall time limit
1.00
120.00 s
15.00
711
-
P2.7.16
Stall frequency limit
1.0
P2.1.2
Hz
25.00
712
-
P2.7.17
Underload protection
0
3
-
0
713
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
3 = Fault, stop by coasting
P2.7.18
Field weakening area load
10.0
150.0
%
50.0
714
-
P2.7.19
Zero frequency load
5.0
150.0
%
10.0
715
-
P2.7.20
Underload protection time
limit
2.00
600.00 s
20.00
716
-
P2.7.21
Response to thermistor
fault
0
3
-
2
732
0 = No response
1 = Warning
2 = Fault, stop acc. to 2.4.7
AB296635287482en-000301 / DPD00903 | 115