Index
Parameter
Min
Max
Unit Default ID
Description
P2.2.35
Reference scaling mini-
mum value, place B
0.00
320.0
Hz
0.00
344
-
P2.2.36
Reference scaling maxi-
mum value, place B
0.00
320.0
Hz
0.00
345
-
P2.2.37
Easy changeover
0
1
-
0
366
0 = Keep reference
1 = Copy actual reference
P2.2.38
(2)
AI3 signal selection
0.1
E.10
-
0.1
141
-
P2.2.39
AI3 signal range
0
1
-
1
143
0 = Signal range 0–10 V
1 = Signal range 2–10 V
P2.2.40
AI3 inversion
0
1
-
0
151
0 = Not inverted
1 = Inverted
P2.2.41
AI3 filter time
0.00
10.00
s
0.10
142
0 = No filtering
P2.2.42
(2)
AI4 signal selection
0.1
E.10
-
0.1
152
-
P2.2.43
AI4 signal range
0
1
-
1
154
0 = Signal range 0–10 V
1 = Signal range 2–10 V
P2.2.44
AI4 inversion
0
1
-
0
162
0 = Not inverted
1 = Inverted
P2.2.45
AI4 filter time
0.00
10.00
s
0.10
153
0 = No filtering
P2.2.46
Actual value special dis-
play minimum
0
30000
-
0
1033 -
P2.2.47
Actual value special dis-
play maximum
0
30000
-
100
1034 -
P2.2.48
Actual value special dis-
play decimals
0
4
-
1
1035 -
P2.2.49
Actual value special dis-
play unit
0
29
-
4
1036 See
10.440 (ID 1036) Actual Value Special Dis-
1
Parameter value can only be changed after the AC drive has been stopped.
2
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
3
Remember to place jumpers of block X2 according to the selection (0, 1 or 2). See the User Manual of the product.
CP = control place
cc = closing contact
oc = opening contact
AB296635287482en-000301 / DPD00903
68 | Danfoss A/S © 2023.02
PID Control Application
VACON® NX All-in-One
Application Guide