Index
Parameter
Min
Max
Unit Default ID
Description
P2.10.6
Torque reference min.
-300.0 300.0
%
100
643
P2.10.7
Torque speed limit (OL)
0
3
1
644
0 = Maximum frequency
1 = Selected frequency ref.
2 = Preset speed 7
P2.10.8
Minimum frequency for open
loop torque control
0.00
P2.1.2
Hz
3.00
636
P2.10.9
Torque controller P gain
0
32000
150
639
P2.10.10 Torque controller I gain
0
32000
10
640
VACON
®
NXP drives only
P2.10.11 Torque speed limit (CL)
0
7
2
1278 0 = CL speed control
1 = Pos/neg freq limits
2 = RampOut (-/+)
3 = NegFreqLimit- RampOut
4 = RampOut-Pos-FreqLimit
5 = RampOut Window
6 = 0-RampOut
7 = RampOut Window On/Off
P2.10.12 Torque reference filtering time
0
32000
ms
0
1244
P2.10.13 Window negative
0.00
50.00
Hz
2.00
1305
P2.10.14 Window positive
0.00
50.00
Hz
2.00
1304
P2.10.15 Window negative off
0.00
P2.10.13 Hz
0.00
1307
P2.10.16 Window positive off
0.00
P2.10.14 Hz
0.00
1306
P2.10.17 Speed control output limit
0.0
300.0
%
300.0
1382
7.4.13 Master Follower Parameters, VACON® NXP (Control Panel: Menu M2 -> G2.11
Table 86: Master Follower Parameters, G2.11
Index
Parameter
Min
Max
Unit Default ID
Description
P2.11.1 Master Follower mode
0
2
-
0
1324 0 = Single drive
1 = Master drive
2 = Follower drive
P2.11.2 Follower stop function
0
2
-
2
1089 0 = Coasting
1 = Ramping
2 = As Master
P2.11.3 Follower speed reference select
0
18
-
18
1081 0 = AI1
1 = AI2
AB296635287482en-000301 / DPD00903 | 121
Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide