Index
Parameter
Min Default ID
Description
P2.3.3.16
(1)
Output frequency limit 1 supervision 0.1
0.1
447
10.75 (ID 315) Output Frequency Limit Supervi-
P2.3.3.17
(1)
Output frequency limit 2 supervision 0.1
0.1
448
10.104 (ID 346) Output Frequency Limit 2 Su-
.
P2.3.3.18
(1)
Reference limit supervision
0.1
0.1
449
10.108 (ID 350) Reference Limit, Supervision
.
P2.3.3.19
(1)
Temperature limit supervision
0.1
0.1
450
10.112 (ID 354) Frequency Converter Tempera-
P2.3.3.20
(1)
Torque limit supervision
0.1
0.1
451
10.106 (ID 348) Torque Limit, Supervision Func-
P2.3.3.21
(1)
Thermistor fault or warning
0.1
0.1
452
-
P2.3.3.22
(1)
Analog input supervision limit
0.1
0.1
453
10.114 (ID 356) Analog Supervision Signal
P2.3.3.23
(1)
Motor regulator activation
0.1
0.1
454
-
P2.3.3.24
(1)
Fieldbus DIN 1
0.1
0.1
455
-
P2.3.3.25
(1)
Fieldbus DIN 2
0.1
0.1
456
-
P2.3.3.26
(1)
Fieldbus DIN 3
0.1
0.1
457
-
P2.3.3.27
(1)
Fieldbus DIN 4
0.1
0.1
169
-
P2.3.3.28
(1)
Fieldbus DIN 5
0.1
0.1
170
-
VACON
®
NXP drives only
P2.3.3.29
(1)
DC ready pulse
0.1
0.1
1218 -
P2.3.3.30
(1)
Safe Disable Active
0.1
0.1
756
-
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
Table 66: Limit Settings (Control Panel: Menu M2 -> G2.3.4)
Index
Parameter
Min
Max
Unit Default ID
Description
P2.3.4.1
Output frequency limit 1 supervision
0
3
-
0
315
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
3 = Brake-on control
P2.3.4.2
Output frequency limit 1; Supervised value
0.00
320.00 Hz
0.00
316
-
P2.3.4.3
Output frequency limit 2 supervision
0
4
-
0
346
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
AB296635287482en-000301 / DPD00903
100 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide