10.73 (ID 313) Relay Output 1 Function
Location in the menu:
P2.3.8
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID
Control Application)
Use this parameter to select the function for the relay output signal.
See
10.72 (ID 312) Digital Output Function
.
10.74 (ID 314) Relay Output 2 Function
Location in the menu:
P2.3.9
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID
Control Application)
Use this parameter to select the function for the relay output signal.
See
10.72 (ID 312) Digital Output Function
.
10.75 (ID 315) Output Frequency Limit Supervision Function
Location in the menu:
P2.3.10
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Applica-
tion)
P2.3.2.1
(Pump and Fan Control Application)
P2.3.4.1
(Multi-Purpose Control Application)
Use this parameter to select the limit supervision function for the output frequency.
If the output frequency goes under/over the set limit (
ID 316
), this function generates a message via digital output depending on:
the settings of parameters
ID 312
to
ID 314
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control
Application) or
to which output the supervision signal 1 (
ID 447
) is connected (Multi-Purpose Control Application, Pump and Fan Control Appli-
cation).
Selection "Brake-on control" is available only for Multi-Purpose Control Application. See
10.620 External Brake Control with Addi-
tional Limits (IDs 315, 316, 346–349, 352, 353)
Brake control uses different output functions. See
10.189 (ID 445) External Brake Control
and
10.190 (ID 446) External Brake Control,
.
10.76 (ID 316) Output Frequency Limit Supervision Value
Location in the menu:
P2.3.11
(Standard Application, Local/Remote Control Application, Multi-Step Speed Control Application, PID Control Applica-
tion)
P2.3.2.2
(Pump and Fan Control Application)
P2.3.4.2
(Multi-Purpose Control Application)
Use this parameter to set the limit supervision value for the output frequency when activating the limit supervision function.
Selects the frequency value supervised by parameter
ID 315
.
AB296635287482en-000301 / DPD00903
192 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide