5.4.3 Input Signals (Control Panel: Menu M2 -> G2.2)
Table 27: Input Signals, G2.2
Index
Parameter
Min
Max
Unit Default ID
Description
P2.2.1
(1)
Place A Start/Stop logic se-
lection
0
6
-
0
300
Logic = 0
Ctrl sgn 1 = Start forward
Ctrl sgn 2 = Start reverse
Logic = 1
Ctrl sgn1 = Start/ Stop
Ctrl sgn 2 = Reverse
Logic = 2
Ctrl sgn 1 = Start/ Stop
Ctrl sgn 2 = Run enable
Logic = 3
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Stop pulse
Logic = 4
Ctrl sgn 1 = Forward pulse (edge)
Ctrl sgn 2 = Reverse pulse (edge)
Logic = 5
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Reverse pulse
Logic = 6
Ctrl sgn 1 = Start pulse (edge)
Ctrl sgn 2 = Enable pulse
P2.2.2
DIN 3 function
0
13
-
1
301 0 = Not used
1 = Ext. fault, closing cont.
2 = Ext. fault, opening cont.
3 = Run enable
4 = Acc./Dec. time select.
5 = Force cp. to I/O
6 = Force cp. to keypad
7 = Force cp. to fieldbus
8 = Rvs (if P2.2.1 ≠ 2,3 or 6)
9 = Jogging speed
10 = Fault reset
11 = Acc./Dec. operation prohibit
12 = DC Braking command
13 = Preset speed
P2.2.3
(2)
AI1 signal selection
0.1
E.10
-
A1
377 -
P2.2.4
(3)
AI1 signal range
0
2
-
0
320 0 = 0–10V (0–20 mA)
1 = 2–10 V (4–20 mA)
2 = Custom setting range
P2.2.5
AI1 custom setting mini-
mum
-160.00 160.00 %
0.00
321 -
P2.2.6
AI1 custom setting maxi-
mum
-160.00 160.00 %
100.00
322 -
AB296635287482en-000301 / DPD00903
50 | Danfoss A/S © 2023.02
Multi-step Speed Control
Application
VACON® NX All-in-One
Application Guide