background image

 

 

Document

 

Category:

 

R

 

&

 

D

 

Doc

                                                 

Confidentiality:

 

 

O

 

open

 

Document

 

Number:

 

UM

DNYS2C

002

                                                                   

 

S

 

Confidential

 

Version:

 

V1.00

                                                                                                       

 

TS

 

Confidential

 

 

 

 

 

DNYS

2C

 

smart

 

key

 

Operating

 

Manual

 

Total

 

30

 

pages

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zhuhai Unitech Power Technology Co., Ltd. 

OCT 20, 2014 

 

Содержание DNYS-2C

Страница 1: ...tegory R D Doc Confidentiality O open Document Number UM DNYS2C 002 S Confidential Version V1 00 TS Confidential DNYS 2C smart key Operating Manual Total 30 pages Zhuhai Unitech Power Technology Co Ltd OCT 20 2014 ...

Страница 2: ...d by Hardware Department hardware representative Chen Pengzhi 2014 10 20 Countersigned by Structure Department Structure Representative Li Qiping 2014 10 20 Countersigned by ProductDevelopment Department Software Representative Tan Yi 2014 10 20 Approved by Product Planning Department product manager Xiu Hongjiang 2014 10 20 Document Revision History Version Summary of modification Modified by App...

Страница 3: ... be copied or disseminated in any form by any means electronically or mechanically including photocopying or recording or for any purpose without written permission of Zhuhai Unitech Power Technology Co Ltd c Copyright 2014 Zhuhai Unitech Power Technology Co Ltd All rights reserved is a registered trademark of Zhuhai Unitech Power Technology Co Ltd ...

Страница 4: ...r operators Structure This Manual contains the following contents general information and features are introduced in the first chapter Product installation and precautions are described in the second chapter The appearance and basic operations as well as each menu to be operated by users are described in the third chapter The defaulting parameter settings are introduced in the fourth chapter Displ...

Страница 5: ...gned to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment doe...

Страница 6: ...URATION 2 CHAPTER 2 INSTALLATION 2 2 1 INSTALLATION STEPS 2 2 2 INSTALLATION CAUTIONS 2 CHAPTER 3 OPERATION 3 3 1 DISPLAY PANEL 3 3 2 OPERATIONS 4 3 2 1 Basic operations 4 3 2 2 Synchronization 5 3 2 3 Receive Operation Orders 6 3 2 4 Unlock 7 3 2 5 Post Back 15 3 2 6 Browse orders 16 3 2 7 Function 17 3 2 8 Settings 19 3 2 9 About 26 ...

Страница 7: ...ERFACE BRIGHTNESS 27 4 4 DISPLAY LANGUAGE 27 4 5 INTERFACE THEMES 27 4 6 SPEAKER STATUS 27 4 7 RECORDING FUNCTION 27 4 8 AUDIO COMPRESSION 27 CHAPTER 5 DISPLAY DESCRIPTIONS 28 CHAPTER 6 PRODUCTS MAINTENANCE 29 6 1 UPGRADE MAINTENANCE 29 6 2 ROUTINE MAINTENANCE 29 6 3 TROUBLESHOOTING 29 ...

Страница 8: ...he applications in centralized control station 1 2 Scope of application Applicable to intetlock of substations power plants etc 1 3 Functions and features The product has the following functions and features 9 Limitless coding and the coding system adopts the GUID 9 Wireless code acquiring the smart key adopts the non contact acquisition mode 9 Black Box function Recording and browsing the operati...

Страница 9: ...high stability convenient extension 9 Integrated mechanism and overall metal frame design to enhance its fall resistance and impact resistance 9 Brand new structure integrating functions such as code acquisition detection and releasing mechanical lock for a simple and convenient operation and the improvement on the stability reliability and productbility 1 4 Model and configuration Product Name sm...

Страница 10: ...ng shock or falling Chapter 3 Operation 3 1 Display Panel 1 Release rod release the mechanical coding lock or other locks 2 Disk determining the rotating direction of release rod in unlocking 3 Conductive electrode powering on locks needing external power supply 4 OLED color screen displaying the operation information by characters and graphics information 5 Keys including the Return key the Switc...

Страница 11: ... the battery symbol is empty indicates the battery runs out please charge the battery immediately icon indicates smart key s current communication mode the above icon means IRDA communication mode icon indicates the current voice state and availability in playing voice The above figure shows enablement state of the function and shows disablement state See specific setting method in the Settings Vo...

Страница 12: ...ubmenu interface press the Cancel key to the standby interface or the option s parent menu z When a user operates on a submenu it can display the scroll bar icon on the right side of the screen to show the current position of the selected submenu 3 2 2 Synchronization The smart key features good interchangeability and versatility it can be applicable to different substations or power plants once s...

Страница 13: ... or Downward key to select the option Receive on the main menu and press Enter it can enter the order receiving interface Then Smart Key can enter order receiving interface directly Thereinto z If the key hasn t synchronized it can not enter the order receiving interface the screen displays the information Without sync cannot receive order and a user must conduct synchronization before receiving o...

Страница 14: ... can display the specific device information under operating while unlocking the mechanical coding locks such as manual disconnector grounding switch and temporary grounding connector web door etc For example if a user wants to 61E line Open Breaker the key can display the following information at this moment Find the corresponding device matched with the displayed by the key on site and insert th...

Страница 15: ...ystem and display below the above is the same to other types of locks At this moment the operator can t unlock because the interlocking gear is locked Please pull out the key and find the correct code before continuing z Unlock the Devices Interlocked by Electric Coding Locks Such as Circuit Breaker Electric Disconnector etc When the smart key displays the device information of circuit breaker or ...

Страница 16: ... If the key is unplugged when it has not detected the complete operation signal over 2 seconds under the operation of electric coding lock it can show as below Press and hold down the success or failure key for 2 seconds to select the operating results success indicates that this step is complete the key can enter the next step failure indicates that this step is not completed and will be restarte...

Страница 17: ...ks Such as Circuit Breaker Electric Disconnector etc z State Detection The smart key shows the state of the device to be detected please find the corresponding connection or disconnection state detectors electrical switching state detectors in accordance with the device number shown on the smart key and insert the smart key the smart key can continue its working only after detecting the correct st...

Страница 18: ...ectriferous detection when the smart key displays electriferous detection and the next option if the electriferous detection is correct and the operation is successful it is available to enter the next step Taking Verified that 73E Breaker has no voltage as an example When the smart key displays the following information in the detecting process ...

Страница 19: ...xed program lock specific types Firstly the fixed program locks can be divided into three types the first type is fixed program lock one way lock unlock and then lock the second type is one way fixed program lock one way lock unlock or lock the third type is fixed program lock two way lock As for the first type fixed program lock one way lock taking 62E Line Open Breaker as an example Insert the k...

Страница 20: ...fixed program lock one way lock taking 62E Line Open Breaker as an example Insert the key into the fixed program lock until the smart key beeps and prompts Correct please operate available in system settings and it displays as follows Rotate the smart key to unlock the smart key prompts the following interface after unlocking is successful then it is available to operate related devices The above ...

Страница 21: ...connecting fixed program locks locking code Take 62E Line Open Breaker as an example Insert the key into the fixed program lock until the smart key beeps and prompts Correct please operate available in system settings and it displays as follows In unlocking process of Close Breaker the first step is disconnecting unlocking after the lock code is verified as correct please rotate the key to unlock ...

Страница 22: ...ration processes and results and other information from the smart key to the mimic panel or integrated operating panel etc When the key completes the current operation order it will automatically prompt the postback information on the completion of operation If the key is closed before postback it can prompt such information again automatically when it restarts the normal postback interface is sho...

Страница 23: ... previous menu z Browse Recall The option is to browse and check the content of the recalling data in the smart key Select the Main Menu Browse Previous to enter the option If the smart key did t have any operating order it will prompt No operation order to review if the smart key have the recalling data press the Enter key to show the content on the first page of the recall records Press the Down...

Страница 24: ...quipment name can be shown if exists If the device name doesn t exist it can show This Dev isn t exist Press the Return key to the previous menu The interface is shown as follows z Advance In the main menu select Function Advance to enter the accessibility menu Skip Skip operation can be defined as to skip the option that has been forcedly operated currently displayed on the smart key when the loc...

Страница 25: ...ils the key displays Please remove the smart key from the skipping key when the skipping operation is successful the smart key loads the next operation automatically and continues its operations Clear Orders If doesn t want to operate an received operating order or post the result back a user can press the Up or Down key to select Advance ClearOdr and press Enter key the key will show the followin...

Страница 26: ...ble operations If a user enters the menu the key will display an interface for inputting password the user can ignore it or press The Return key to the previous menu the operating interface is as shown as below z Internal This menu provides a series of debugging programs special for production personal and such test options are unavailable to final users for further safe and reliable operations If...

Страница 27: ...ceFunc to enter this menu and then set voice related options by operating various sub menus SetVoice Select VoiceFunc SetVoice to enter Voice Settings interface and press the Close button or the Open button to disenable or enable voice setting state or check voice setting status by small icons as shown below RecSet Select VoiceFunc RecSet to enter Recording Settings interfaces and press the Close ...

Страница 28: ...unction After the function is enabled the system will compress and save recorded audio thus saving memory space RecCopy Select VoiceFunc RecCopy to enter Copy recording interface and press the Close button or the Open button to disenable or enable the function After the function is enabled connect smart keys to PC via USB cable a U disk icon will appear on PC which is read only enter the U disk to...

Страница 29: ...lose button or the Open button to disenable or enable the function the recording process is shown below Enter the menu and wait for recording Press the Record button to start up recording Press the Stop button to stop recording waiting for the next recording or press Back key to return ...

Страница 30: ...n menu to enter the menu Press the arrow keys to increase or decrease the backlight brightness press the Enter key to save the current backlight brightness level Press the Cancel key to the previous menu z Time The menu functions as setting time and date Select Settings Time on the main menu to enter the menu as shown as below Date Setting Select Time Date to enter the option and then move the cur...

Страница 31: ...g is completed z Background The menu functions as setting the background pattern of the user interface Select Settings Background to enter the menu as shown as below Press the Up or Down key to select the background image press the Enter key to set press the Return key to cancel the operation The currently available backgrounds are two options as follows theme 2 is not available currently ...

Страница 32: ...nter the option and the optional languages include Chinese and English Chinese Select Language Chinese to enter and press the Enter key to select the Chinese English Select Language English to enter and press the Enter key to select the English ...

Страница 33: ...26 3 2 9 About Enter this option to check the software version model number and manufacturer name Thereinto A user can press the return key directly to the main menu interface ...

Страница 34: ...n sleep mode and its screen will become black and indicator can flashes green periodically If any button is pressed or the key start receiving operation orders or synchronization the key will exit the automatic sleep mode light up the screen and display interface 4 3 Interface Brightness Under default conditions the screen brightness is 6 4 4 Display Language The default interface language is Engl...

Страница 35: ... unavailable to receive operating order Without sync cannot receive order The key should not receive operating order unless completing synchronization Creat or open file error file system is abnormal Receive the data error Error occurs during order receiving and synchronization the key will automatically delete incorrect data RFID code is not sorted in descending order RFID sequence isn t correct ...

Страница 36: ...ment Mechanical coding lock is opened but unlocking program cannot continue 1 The internal IRDA device of the smart key is damaged 2 Unlocking stem is offset 1 Send the smart key back to Zhuhai Unitech Power Technology Co Ltd for repairing 2 Re adjust the horizontal position or send it back to our company The smart key cannot receive the operation order sent from the transmission port 1 The smart ...

Страница 37: ...ng lock can be opened 1 Internal relay of the smart key is damaged 2 The battery voltage is low 3 The smart key is in an improper connection to the electric coding lock 1 Send the smart key back to Zhuhai Unitech Power Technology Co Ltd 2 Ensure charge adequate power before operating the smart key 3 Clear the conductivity pole of the electric coding lock and renew the electric coding lock if neces...