10.170 (ID 426) Autochange 1 Interlock
Location in the menu:
P2.2.7.18
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-Pump system.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact closed: Interlock of autochange drive 1 or auxiliary drive 1 activated.
Default programming: A.2.
10.171 (ID 427) Autochange 2 Interlock
Location in the menu:
P2.2.7.19
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-Pump system.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact closed: Interlock of autochange drive 2 or auxiliary drive 2 activated.
Default programming: A.3.
10.172 (ID 428) Autochange 3 Interlock
Location in the menu:
P2.2.7.20
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-Pump system.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact closed: Interlock of autochange drive 3 or auxiliary drive 3 activated.
10.173 (ID 429) Autochange 4 Interlock
Location in the menu:
P2.2.7.21
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-Pump system.
Contact closed: Interlock of autochange drive 4 or auxiliary drive 4 activated.
10.174 (ID 430) Autochange 5 Interlock
Location in the menu:
P2.2.7.22
(Pump and Fan Control Application)
Use this parameter to select the digital input signal that is used as interlock signal for the Multi-Pump system.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact closed: Interlock of autochange drive 5 activated.
10.175 (ID 431) PID Reference 2
Location in the menu:
P2.2.7.23
(Pump and Fan Control Application)
Use this parameter to select the source of the PID setpoint signal.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
Contact open: PID controller reference selected with parameter
ID 332
.
Contact closed: PID controller keypad reference 2 selected with parameter
ID 371
.
10.176 (ID 432) Ready
Location in the menu:
P2.3.3.1
(Multi-purpose Control Application)
P2.3.1.1
(Pump and Fan Control Application)
Use this parameter to select a digital output for the
Ready
status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
10.177 (ID 433) Run
Location in the menu:
P2.3.3.2
(Multi-purpose Control Application)
P2.3.1.2
(Pump and Fan Control Application)
Use this parameter to select a digital output for the
Run
status.
TTF programming method must be applied to this parameter (see
10.626 "Terminal to Function" (TTF) Programming Principle
AB296635287482en-000301 / DPD00903
220 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide