Index
Parameter
Min
Max
Unit Default ID
Description
Ctrl sgn 1 = Start forward (edge)
Ctrl sgn 2 = Start reverse (edge)
Logic = 6
Ctrl sgn 1 = Start (edge) / Stop
Ctrl sgn 2 = Reverse
Logic = 7
Ctrl sgn 1 = Start (edge) / Stop
Ctrl sgn 2 = Run enable
Logic = 8
Ctrl sgn 1 = Start forward (edge)
Ctrl sgn 2 = Motor potentiometer UP
P2.2.2
DIN 3 function
0
13
-
1
301 0 = Not used
1 = Ext. fault, closing cont.
2 = Ext. fault, opening cont.
3 = Run enable
4 = Acc./Dec. time selection
5 = Force cp. to I/O
6 = Force cp. to keypad
7 = Force cp. to fieldbus
8 = Reverse
9 = Jogging speed
10 = Fault reset
11 = Acc./Dec. operation prohibit
12 = DC Braking command
13 = Motor potentiometer DOWN
P2.2.3
(2)
AI1 signal selection
0.1
E.10
-
A1
377 -
P2.2.4
(3)
AI1 signal range
0
2
-
0
320 0 = 0–10 V (0–20 mA)
1 = 2–10 V (4–20 mA)
2 = Custom setting range
P2.2.5
AI1 custom setting minimum
-160.00 160.00 %
0.00
321 -
P2.2.6
AI1 custom setting maximum
-160.00 160.00 %
0.00
322 -
P2.2.7
AI1 signal inversion
0
1
-
0
323 0 = Not inverted
1 = Inverted
P2.2.8
AI1 signal filter time
0.00
10.00
s
A1
324 -
P2.2.9
(2)
AI2 signal selection
0.1
E.10
-
A.2
388 -
P2.2.10
(3)
AI2 signal range
0
2
-
1
325 0 = 0–10 V (0–20 mA)
1 = 2–10 V (4–20 mA)
2 = Custom setting range
P2.2.11
AI2 custom setting minimum
-160.00 160.00 %
0.00
326 -
P2.2.12
AI2 custom setting maximum
-160.00 160.00 %
100.00
327 -
AB296635287482en-000301 / DPD00903 | 35
Danfoss A/S © 2023.02
Local/Remote Control Application
VACON® NX All-in-One
Application Guide