Use this parameter to select the operation for the wake-up level parameter.
This parameter defines whether the restoration of the Run state occurs when the actual value signal falls below or exceeds the
Wake-up level
(parameter
ID 1018
). See
10.422 (ID 1018) Wake Up Level
and
The PID Control Application has selections 0–1 and Pump and Fan Control Application selections 0–3 available.
Selec-
tion
number
Function
Limit
Description
0
Wake-up happens
when actual value goes
below the limit.
The limit defined with parameter
ID 1018 is in percent of the maxi-
mum actual value.
100%
Actual
value
signal
t
Start
Stop
Par. ID1018=30%
e
3
0
b
h
0
7
1
.1
0
1
Wake-up happens
when actual value ex-
ceeds the limit.
The limit defined with parameter
ID 1018 is in percent of the maxi-
mum actual value.
100%
Actual
value
signal
t
Start
Stop
Par. ID1018=60%
e
3
0
b
h
0
7
2
.1
0
AB296635287482en-000301 / DPD00903 | 271
Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide