Index
Parameter
Min
Max
Unit Default
ID
Description
3 = Wake-up at exceeded wake-up
level (P3.4/P3.5)
P2.1.19
Jogging speed reference
0.00
P2.1.2
Hz
10.00
124
-
1
Use the Terminal to Function method (TTF) with these parameters, see
10.626 "Terminal to Function" (TTF) Programming Principle
).
8.4.3 Input Signals
Table 92: Basic Settings (Control Panel: Menu M2 -> G2.2.1)
Index
Parameter
Min
Max
Unit Default ID
Description
P2.2.1.1
(1)
I/O B frequency refer-
ence selection
0
7
-
0
343 0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = Keypad reference
5 = Fieldbus reference (FB SpeedReference)
6 = Motor potentiometer
7 = PID controller
P2.2.1.2
(1)
Keypad control refer-
ence selection
0
7
-
4
121
P2.2.1.3
(1)
Fieldbus control ref-
erence selection
0
7
-
5
122
P2.2.1.4
(1)
PID Reference 2
0
7
-
7
371 0 = AI1
1 = AI2
2 = AI3
3 = AI4
4 = PID reference 1 from keypad
5 = Fieldbus reference (FBProcess- DataIN3)
6 = Motor potentiometer
7 = PID reference 2 from keypad
P2.2.1.5
PID error value inver-
sion
0
1
-
0
340 0 = No inversion
1 = Inversion
P2.2.1.6
PID reference rising
time
0.1
100.0
s
5.0
341 -
P2.2.1.7
PID reference falling
time
0.1
100.0
s
5.0
342 -
P2.2.1.8
(1)
PID actual value se-
lection
0
7
-
0
333 0 = Actual value 1
1 = Actual 1 + Actual 2
2 = Actual 1 - Actual 2
3 = Actual 1 * Actual 2
4 = Max (Actual 1, Actual 2)
5 = Min (Actual 1, Actual 2)
6 = Mean (Actual 1, Actual 2)
7 = Sqrt (Act1) + Sqrt (Act2) See P2.2.1.9 and
P2.2.1.10
P2.2.1.9
(1)
Actual value 1 selec-
tion
0
5
-
2
334 0 = Not used
1 = AI1 (control board)
2 = AI2 (control board)
AB296635287482en-000301 / DPD00903 | 135
Danfoss A/S © 2023.02
Pump and Fan Control Application
VACON® NX All-in-One
Application Guide