Index
Parameter
Min
Max
Unit Default ID
Description
3 = Brake-off control
4 = Brake on/off control
P2.3.4.4
Output frequency limit 2; Supervised value
0.00
320.00 Hz
0.00
347
-
P2.3.4.5
Torque limit supervision
0
3
-
0
348
0 = No supervision
1 = Low limit supervision
2 = High limit supervision
3 = Brake-off control
P2.3.4.6
Torque limit supervision value
-300.0 300.0
%
100.0
349
-
P2.3.4.7
Reference limit supervision
0
2
-
0
350
0 = No supervision
1 = Low limit
2 = High limit
P2.3.4.8
Reference limit supervision value
0.0
100.0
%
0.0
351
0.0 = Min frequency
100.0 = Max frequency
P2.3.4.9
External brake-off delay
0.0
100.0
s
0.5
352
-
P2.3.4.10
External brake-on delay
0.0
100.0
s
1.5
353
-
P2.3.4.11
Temperature limit supervision
0
2
-
0
354
0 = No supervision
1 = Low limit
2 = High limit
P2.3.4.12
Temperature supervised value
-10
100
°C
40
355
-
P2.3.4.13
Analog supervision signal
0
4
-
0
356
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
P2.3.4.14
Analogue supervision low limit
0.00
100.00 %
100.00
357
See P2.3.3.22.
P2.3.4.15
Analog supervision high limit
0.00
100.00 %
90.00
358
See P2.3.3.22.
VACON
®
NXP drives only
P2.3.4.16
Brake On/Off Current Limit
0
2 x I
H
A
0
1085 -
Table 67: Analog Output 1 (Control Panel: Menu M2 -> G2.3.5)
Index
Parameter
Min
Max
Unit De-
fault
Cust ID
Description
P2.3.5.1
(1)
Analog output 1
signal selection
0.1
E.10
-
A.1
-
464 -
P2.3.5.2
Analog output 1
function
0
15
-
1
-
307 0 = Not used (20 mA / 10 V)
1 = Output freq. (0–f
max
)
AB296635287482en-000301 / DPD00903 | 101
Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide