4.2 Control I/O in Local/Remote Control Application
Reference potentiometer,
1-10kΩ
1
6
2
3
4
5
18
19
20
12
7
13
8
9
10
14
15
16
21
22
23
11
17
24
25
26
mA
Remote Reference
0(4) - 20 mA
RUN
READY
AO1-
DO1
+24 V
GND
GND
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
RO1
RO1
RO1
CMA
CMB
RO2
RO2
RO2
OPTA1
OPTA2 / OPTA3
Terminal
Signal
Description
+10 V
ref
AI1+
AI1-
AI2+
AI2-
+24V
Reference output
I/O Ground
Analogue input 2
Current range
0—20mA
Programmable
(P2.1.11)
Control voltage output
I/O ground
Place A: Start forward
Programmable logic (P2.2.1)
Place A: Start reverse
Ri min = 5 kohm
External fault input
Programmable (P2.2.2)
Place B: Start forward
Programmable logic (P2.2.15)
Place B: Start reverse
Ri min = 5 kΩ
Place A/B selection
Common for DIN 1—DIN 3
Common for DIN4—DIN6
Control voltage output
I/O ground
Analogue output 1
Output frequency
Programmable (P2.3.2)
Digital output
READY
Programmable (P2.3.7)
Open collector,
I≤50 mA, U≤48 VDC
Relay output 1
RUN
Programmable
(P2.3.8)
Relay output 2
FAULT
Programmable
(P2.3.9)
Range 0—20 mA/R
L
,
max. 500 Ω
Contact open = place A is active
Contact closed = Place B is active
Contact closed
= start forward
Contact closed
= start reverse
AO1+
Analogue input 1
reference for place B
Ground for reference
and controls
Analogue input 2
reference for place A
Contact closed = start forward
Contact closed = start reverse
Contact open = no fault
Contact closed = fault
Voltage for potentiometer, etc.
Analogue input 1
Voltage range 0—10V DC
Programmable (P2.1.12)
Voltage for switches,
etc. max 0.1 A
Voltage for switches (see #6)
Connect to GND or +24 V
Connect to GND or +24 V
Ground for reference and controls
Ground for reference and controls
e3
0b
h0
92
.2
0
Illustration 8: Default I/O Configuration in Local/Remote Control Application
The option board OPTA3 has no terminal for open contact on its second relay output (terminal 24 is missing).
See jumper selections in
. More information in the User Manual of the product.