Setting the parameter to 0 deactivates the protection and reset the stall time counter. See
10.622 Parameters of Stall Protection (IDs
10.342 (ID 710) Stall Current
Location in the menu:
P2.7.11
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application
Use this parameter to set the limit above which the current of the motor must stay for a stall stage to occur.
The value of this parameter can be set between 0.0 and 2*I
H
. For a stall status to occur, the current must be higher than this limit. If
parameter
ID 107
Nominal current limit of motor changes, this parameter is automatically calculated to 90% of the current limit. See
10.622 Parameters of Stall Protection (IDs 709–712)
The value of the Stall Current must be below the motor current limit.
f
I
ID710
ID712
A
e
3
0
b
u
0
6
3
Illustration 75: The Stall Characteristics Settings
A
Stall area
10.343 (ID 711) Stall Time Limit
Location in the menu:
P2.7.15
(Standard Application, Local/Remote Control Application, Multi-step Speed Control Application, PID
Control Application, Multi-purpose Control Application, Pump and Fan Control Application
Use this parameter to set the maximum time for a stall stage.
This parameter is the maximum time for the stall stage to be active before a motor stall fault occurs. The value of this parameter can
be set between 1.0 s and 120.0 s. An internal counter counts the stall time. If the stall time counter value goes above this limit, the
protection causes the drive to trip.
See
10.622 Parameters of Stall Protection (IDs 709–712)
AB296635287482en-000301 / DPD00903
254 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide