Index
Parameter
Min
Max
Unit Default ID
Description
2 = AI1+AI2
3 = AI1-AI2
4 = AI2-AI1
5 = AI1xAI2
6 = AI1 Joystick
7 = AI2 Joystick
8 = Keypad
9 = Fieldbus
10 = Motor potentiometer
11 = AI1, AI2 minimum
12 = AI1, AI2 maximum
13 = Max frequency
14 = AI1/AI2 selection
15 = Encoder 1 (C. 1)
16 = Encoder 2 (C. 3)
17 = Master Reference
18 = Master Ramp Out
P2.11.4 Follower torque reference select 0
9
-
9
1083 0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = AI1 joystick
6 = AI2 joystick
7 = Torque reference from keypad, R3.5
8 = FB Torque Reference
9 = Master torque
P2.11.5 Speed share
-300.00 300.00 %
100.0
1241 -
P2.11.6 Load share
0.0
500.0
%
100.0
1248 -
P2.11.7 Master Follower mode 2
0
2
-
0
1093 0 = Single drive
1 = Master drive
2 = Follower drive
P2.11.8 Follower fault
0
2
-
0
1536 0 = Single drive
1 = Master drive
2 = Follower drive
7.4.14 Functional Safety (Control Panel: Menu M2 -> G.12)
Table 87: Functional Safety Parameters, G2.12
Index
Parameter
Min Max Unit De-
fault
ID
Description
P2.12.1 Response to safe
stop request
0
3
-
0
542 0 = No action
1 = Stop by ramping, according to P2.1.4
2 = Stop by ramping, according to P2.4.4
AB296635287482en-000301 / DPD00903
122 | Danfoss A/S © 2023.02
Multi-purpose Control Application
VACON® NX All-in-One
Application Guide