P2.1.14
(Multi-Step Speed Control Application, Multi-Purpose Control Application)
P2.1.15
(Local/Remote Control Application)
P2.1.19
(PID Control Application, Pump and Fan Control Application)
Use this parameter to set the jogging frequency reference when the jogging speed function is in use.
Defines the jogging speed reference when activated by digital input. See parameter
ID 301
and
ID 413
.
The parameter value is automatically limited to
Maximum frequency
(
ID 102
).
10.23 (ID 125) Control Place
Location in the menu:
P3.1
Use this parameter to select the control place.
For more information, see the User manual product.
Pushing the Start button for 3 s selects the control panel as the active control place and copies the Run status information (Run/
Stop, direction, and reference).
10.24 (ID 126) Preset Speed 3
Location in the menu:
P2.1.17
(Multi-Step Speed Control Application, Multi-Purpose Control Application)
Use this parameter to set the preset speed reference when the preset speed function is used.
For more information, see
10.25 (ID 127) Preset Speed 4
Location in the menu:
P2.1.18
(Multi-Step Speed Control Application, Multi-Purpose Control Application)
Use this parameter to set the preset speed reference when the preset speed function is used.
For more information, see
10.26 (ID 128) Preset Speed 5
Location in the menu:
P2.1.19
(Multi-Step Speed Control Application, Multi-Purpose Control Application)
Use this parameter to set the preset speed reference when the preset speed function is used.
For more information, see
10.27 (ID 129) Preset Speed 6
Location in the menu:
P2.1.20
(Multi-Step Speed Control Application, Multi-Purpose Control Application)
Use this parameter to set the preset speed reference when the preset speed function is used.
For more information, see
10.28 (ID 130) Preset Speed 7
Location in the menu:
P2.1.21
(Multi-Step Speed Control Application, Multi-Purpose Control Application)
Use this parameter to set the preset speed reference when the preset speed function is used.
These parameters can be used to determine frequency references that are applied when appropriate combinations of digital inputs
are activated.
In Multi-Step Speed Application (Application 4), digital inputs DIN 4, DIN 5, and DIN 6 are assigned to Preset Speed functions. The
combinations of these activated inputs select the preset speed reference.
Note the use of TTF-programming method in the Multi-purpose Control Application. Because all digital inputs are programmable,
first assign three DINs for the Preset Speed functions (parameters
ID 419
,
ID 420
, and
ID 421
.
Speed
DIN 4/ID 419
DIN 5/ID 420
DIN 6/ID 421
Basic speed
0
0
0
Preset speed 1 (ID 105)
1
0
0
Preset speed 2 (ID 106)
0
1
0
Preset speed 3 (ID 126)
1
1
0
Preset speed 4 (ID 127)
0
0
1
AB296635287482en-000301 / DPD00903
174 | Danfoss A/S © 2023.02
Parameter Descriptions
VACON® NX All-in-One
Application Guide