P 9.4.4.5 T18 Pulse Filter Time Constant
Enter the pulse filter time constant. The low-pass filter reduces the influence on and dampens oscillations on the feedback signal from
the control. This is an advantage, for example, if there is a great amount on noise in the system.
Default value:
100
Parameter type:
Range (1–1000)
Parameter
number:
559
Unit:
ms
Data type:
uint16
Access type:
Read/Write
Variable duty cycle pulse signal as input
The normal pulse input has fixed 50% duty cycle. To enable variable duty cycle pulse signal as the reference, the terminal 18 must be set
for variable duty cycle pulse signal as input.
P 9.4.1.6 T18 Digital Input
should be set as
[46] Pulse PWM Input
. The related parameters for
reference source
P 5.5.3.x
should be selected as
[8] Frequency Input 18
. The frequency range of pulse input is from 1 Hz to 1 kHz.
Parameter P 9.4.4.6 T18 PWM Polarity
is for selecting the polarity of pulse input signal. Select
[0] Positive
for positive direction pulses.
Select
[1] Negative
for negative direction pulses.
P 9.4.4.7 T18 High Duty
is the duty cycle of pulse corresponding to the high reference
value in
P 9.4.4.3 Term. 18 High Ref./Feedb. Value
.
P 9.4.4.8 T18 Low Duty
is the duty cycle of pulse corresponding to the low reference
value in
P 9.4.4.4 Term. 18 Low Ref./Feedb. Value
.
P 9.4.4.6 T18 PWM Polarity
When setting the variable duty cycle pulse signal as the reference, use this parameter to select the activated PWM polarity. Select
[0]
Positive
, for positive direction pulses. Select
[1] Negative
, for negative direction pulses.
Default value:
0
Parameter type:
Selection
Parameter
number:
505
Unit:
–
Data type:
enum
Access type:
Read/Write
Selection number
Selection name
0
Positive
1
Negative
P 9.4.4.7 T18 High Duty
When setting variable duty cycle pulse signal as the reference, use this parameter to enter the pulse PWM input high duty (%) that
corresponds to the high reference value in
P 9.4.4.3 Term. 18 High Ref./Feedb. Value
.
Default value:
5000
Parameter type:
Range (100–10000)
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
245
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......