Application Guide | iC2-Micro Frequency Converters
Table 37: Drive Status Word (FC Profile)
(continued)
Coil
0
1
47
Not in current limit
Current limit
48
No thermal warning
Thermal warning
Address/Registers
Table 38: Address/Registers
Bus address
Bus register
(1)
PLC register
Content
Access
Description
0
1
40001
Reserved
–
Reserved for legacy
drives
1
2
40002
Reserved
–
Reserved for legacy
drives
2
3
40003
Reserved
–
Reserved for legacy
drives
3
4
40004
Free
–
–
4
5
40005
Free
–
–
5
6
40006
Modbus configura-
tion
Read/Write
TCP only. Reserved
for Modbus TCP
6
7
40007
Last fault code
Read only
Fault code received
from parameter
database
7
8
40008
Last error register
Read only
Address of register
with which last er-
ror occurred.
8
9
40009
Index pointer
Read/Write
Subindex of pa-
rameter to be ac-
cessed.
9
10
40010
Dependent on pa-
rameter access
20 bytes space re-
served for parame-
ter in Modbus map.
29
30
40030
Dependent on pa-
rameter access
20 bytes space re-
served for parame-
ter in Modbus map.
1) Value written in the Modbus RTU telegram must be 1 or less than the register number. For example, Read Modbus Register 1 by writing value 0 in the telegram.
6.1.7.5
How to Access Parameters
6.1.7.5.1
Parameter Handling
The PNU (parameter number) is translated from the register address contained in the Modbus read or write telegram. The parameter
number is translated to Modbus as (10 * parameter number-1) decimal.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |