Output freq.
STW
Follower-master
e3
0b
a2
73
.1
1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit
no.:
Figure 66: Status Word
Table 56: Status Word According to FC Profile
Bit
Bit = 0
Bit = 1
00
Control not ready
Control ready
01
Drive not ready
Drive ready
02
Coasting
Enable
03
No error
Trip
04
No error
Error (no trip)
05
Reserved
–
06
No error
Triplock
07
No warning
Warning
08
Speed≠reference
Speed=reference
09
Local operation
Bus control
10
Out of frequency limit
Frequency limit OK
11
No operation
In operation
12
Drive OK
Stopped, auto start
13
Voltage OK
Voltage exceeded
14
Torque OK
Torque exceeded
15
Timer OK
Timer exceeded
6.1.8.4
Explanation of Status Word Bit
Bit 00, Control Not Ready/Ready
Bit 00=0: The drive trips.
Bit 00=1: The drive controls are ready but the power component does not necessarily receive any supply (if there is 24 V external supply
to controls).
Bit 01, Drive Ready
Bit 01=0: The drive is not ready.
Bit 01=1: The drive is ready for operation, but the coasting command is active via the digital inputs or via serial communication.
Bit 02, Coast Stop
Bit 02=0: The drive releases the motor.
100
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters