Application Guide | iC2-Micro Frequency Converters
WARNING/FAULT 4, Mains Phase Loss
Cause
A phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input
rectifier. Options are programmed in
P 1.3.1 Mains Imbalance Function
.
Troubleshooting
l
Check the supply voltage and supply currents to the drive.
WARNING/FAULT 7, DC Overvoltage
Cause
If the DC-link voltage exceeds the limit, the drive trips after a time.
Troubleshooting
l
Extend the ramp time.
l
Change the ramp type.
WARNING/FAULT 8, DC Under Voltage
Cause
If the DC-link voltage (DC) drops below the undervoltage limit, the drive trips after a fixed time delay. The time delay varies with unit size.
Troubleshooting
l
Check that the supply voltage matches the drive voltage.
l
Perform the input voltage test.
l
Perform the soft charge circuit test.
WARNING/FAULT 9, Inverter Overload
Cause
The drive is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter
protection issues a warning at 90% and trips at 100%, while giving a FAULT. The drive cannot be reset until the counter is below 0%.
The fault occurs when the drive has run with more than 100% overload for too long.
Troubleshooting
l
Compare the output current shown on the control panel with the drive rated current.
l
Compare the output current shown on the control panel with measured motor current.
l
Show the thermal drive load on the control panel and monitor the value. When running above the drive continuous current rating,
the counter increases. When running below the drive continuous current rating, the counter decreases.
WARNING/FAULT 10, Motor Overload Temperature
Cause
According to the electronic thermal protection (ETR), the motor is too hot. Select whether the drive issues a warning or an alarm when
the counter reaches 100% in
P 4.6.7 Motor Thermal Protection
. The fault occurs when the motor runs with more than 100% overload for
too long.
Troubleshooting
l
Check if the motor is overheating.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
267
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......