NOTICE
In automatic reset mode, the motor can start without a warning.
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
Manual reset
Perform a reset via
Stop/Reset
button or via the digital inputs.
1
Automatic reset x 1
2
Automatic reset x 2
3
Automatic reset x 3
4
Automatic reset x 4
5
Automatic reset x 5
6
Automatic reset x 6
7
Automatic reset x 7
8
Automatic reset x 8
9
Automatic reset x 9
10
Automatic reset x 10
11
Automatic reset x 15
12
Automatic reset x 20
13
Infinite auto reset
Select for continuous resetting after tripping.
14
Reset at power-up
NOTICE
If the specified number of automatic resets is reached within 10 minutes, the frequency converter enters
[0] Manual Reset Mode
.
After the manual rest is performed, the setting of
P 6.6.6 Reset Mode
reverts to the original selection. If the number of automatic
resets is not reached within 10 minutes, or when a manual reset is performed, the internal automatic reset counter returns to 0.
P 6.6.7 Automatic Restart Time
Use this parameter to enter the time interval from the trip event to the automatic reset. This parameter is active when
P 6.6.6 Reset Mode
is set to a selection between [1]–[13].
Default value:
10
Parameter type:
Range (0–600)
Parameter
number:
1421
Unit:
s
Data type:
uint16
Access type:
Read/Write
NOTICE
A value of 0s cannot be set when
P 6.6.6 Reset Mode
is set to
[13] Infinite auto reset
.
194
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......