Application Guide | iC2-Micro Frequency Converters
Selection number
Selection name
Selection description
45
Latched Start Reverse
The motor starts to run reverse when a pulse is applied for
minimum 4 ms. The motor stops when stop commands are
given.
46
Pulse PWM Input
To enable variable duty cycle pulse signal as the reference.
51
External Interlock
This function makes it possible to give an external fault to
the frequency converter. This fault is treated as an internally
generated fault.
60
Counter A (up)
Input for increment counting in the SLC counter A.
61
Counter A (down)
Input for decrement counting in the SLC counter A.
62
Reset Counter A
Input for reset of counter A.
63
Counter B (up)
Input for increment counting in the SLC counter B.
64
Counter B (down)
Input for decrement counting in the SLC counter B.
65
Reset Counter B
Input for reset of counter B.
101
Sleep
A signal applied puts the frequency converter into sleep mode.
Time [sec]
a
b
e3
0b
b
46
2.
12
Speed [RPM]
Time [sec]
Speed [RPM]
Read timer:
20 timer tides
Read timer:
20 timer tides
Time start
Time counter
Sample time
Timer
Pulse
e3
0b
b
46
4.
11
Figure 81: Duration between Pulse Flanks
7.9.2.2
T15 as Digital Output (Menu Index 9.4.2)
P 9.4.2.1 T15 Mode
Select
[0] Input
to define terminal 15 as a digital input. Select
[1] Output
to define terminal 15 as a digital output.
Default value:
0 [Input]
Parameter type:
Selection
Parameter
number:
501
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
235