Application Guide | iC2-Micro Frequency Converters
Table 20: Default Settings
Category
Parameter index
Parameter name
Default setting
Parameter number
Operation mode
5.4.2
Operation Mode
[4] Torque Open Loop
100
DI 1 - T13
9.4.1.2
T13 Digital Input
[8] Start
510
DI 2 - T14
9.4.1.3
T14 Digital Input
[0] No operation
511
DI/O - T15
9.4.1.4
T15 Digital Input
[1] Reset
512
DI 3 - T17
9.4.1.5
T17 Digital Input
[14] Jog
513
DI 4 - T18
9.4.1.6
T18 Digital Input
[0] No Operation
515
9.5.2.1
T33 Mode
[1] Voltage Mode
619
9.5.2.2
T33 High Voltage
10V
611
9.5.2.3
T33 Low Voltage
0.07V
610
9.5.2.6
T33 High Ref./Feedb.
Value
The value should be
set manually accord-
ing to application re-
quirement.
615
AI1 - T33
9.5.2.7
T33 Low Ref./Feedb.
Value
0
614
9.5.3.1
T34 Mode
[0] Current Mode
629
9.5.3.4
T34 High Current
20.00 mA
623
9.5.3.5
T34 Low Current
4.00 mA
622
9.5.3.6
T34 High Ref./Feedb.
Value
50. If
[1] North Amer-
ica
is selected for
P 1.2.1 Regional
Settings
, the default
value is 60.
625
AI2 - T34
9.5.3.7
T34 Low Ref./Feedb.
Value
0
624
9.5.1.1
T31 Mode
[0] 0-20 mA
690
AO1 - T42
9.5.1.2
T31 Analog Output
[100] Output Fre-
quency
691
Relay
9.4.3.1
Function Relay
[9] Fault
540
5.5.3.5
Reference Function
[0] Sum
304
5.5.3.7
Reference 1 Source
[1] Analog Input 33
315
5.5.3.8
Reference 2 Source
[0] No Function
316
External reference
5.5.3.9
Reference 3 Source
[11] No Function
317
Speed Limit
5.10.3
Speed Limit Mode
Torque Ctrl.
[0] No Function
421
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
65
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......