The 2 types of reference inputs are combined in the following formula:
Remote reference=X+X*Y/100%
If relative reference is not used, set
P 5.5.3.12 Relative Scaling Reference Resource
to
[0] No function
and
P 5.5.3.11 Preset Relative
Reference
to 0%. The digital inputs on the drive can activate both the catch up/slow down function and the freeze reference function.
5.6.2
Reference Limits
The reference range, minimum reference, and maximum reference define the allowed range of the sum of all references. The sum of all
references is clamped when necessary. The relation between the resulting reference (after clamping) and the sum of all references are
shown in
.
e3
0b
k0
91
.1
0
Reference range = Minimum to maximum
Resulting reference
Forward
Reverse
Maximum reference
Minimum reference
-Minimum reference
-Maximum reference
Sum of all
references
Figure 44: Reference Range is Set to 0
e3
0b
h3
25
.1
0
Reference range = -Maximum to +maximum
Resulting reference
Maximum reference
-Maximum reference
Sum of all
references
Figure 45: Reference Range is Set to 1
The minimum reference cannot be set to less than 0, unless the configuration mode is set to Process. In that case, the following relations
between the resulting reference (after clamping) and the sum of all references are as shown in
68
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters