Parameter
number:
507
Unit:
%
Data type:
uint16
Access type:
Read/Write
P 9.4.4.8 T18 Low Duty
When setting variable duty cycle pulse signal as the reference, use this parameter to enter the pulse PWM input low duty (%) that
corresponds to the low reference value in
P 9.4.4.4 Term. 18 Low Ref./Feedb. Value
.
Default value:
0
Parameter type:
Range (0–9900)
Parameter
number:
506
Unit:
%
Data type:
uint16
Access type:
Read/Write
7.9.2.5
T15 as Pulse Output (Menu Index 9.4.5)
P 9.4.5.1 T15 Pulse Output Variable
Select the desired output on terminal 15.
Default value:
0
Parameter type:
Selection
Parameter
number:
560
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
0
No Operation
45
Bus Control
48
Bus Control, Timeout
100
Output Frequency
101
Reference
102
Process Feedback
103
Motor Current
104
Torque Relate to Limit
105
Torque Relate to Rated
106
Power
107
Speed
109
Max Out Frequency
113
PID Clamped Output
246
| Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254
Application Guide | iC2-Micro Frequency Converters