Application Guide | iC2-Micro Frequency Converters
Table 17: Default Settings
(continued)
Category
Parameter index
Parameter name
Default setting
Parameter number
5.5.3.7
Reference 1 Source
[0] No Function
315
5.5.3.8
Reference 2 Source
[0] No Function
316
External reference
5.5.3.9
Reference 3 Source
[0] No Function
317
Preset refer.
5.5.3.10
Preset Reference
Note:
Set as array
type
.
310
5.9.2
Jog Reference
5.0
311
Jog
5.9.1
Jog Ramp Time
3 s
380
5.5.3.3
Reference Maximum
50. If
[1] North Amer-
ica
is selected for
P 1.2.1 Regional
Settings
, the default
value is 60.
303
Reference limits
5.5.3.4
Reference Minimum
0
302
Table 18:
Parameter P 5.5.3.10 Preset Reference
Setting (Array Type)
DI4 (Terminal 18)
DI3 (Terminal 17)
Reference
[17] Preset Ref Bit [1]
[16] Preset Ref Bit [0]
Preset Reference 0
0
0
Preset Reference 1
0
1
Preset Reference 2
1
0
Preset Reference 3
1
1
5.5.5
Configuring Wire Control Mode
3-Wire Control Mode of the drive enables to imitate the common contactor control circuit to control the motor. This is possible by using
2 momentary push-buttons to control motor start and motor stop. Reversing is controlled by 1 digital input.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |