Application Guide | iC2-Micro Frequency Converters
Table 16: Process Control Mode Default Settings
(continued)
Category
Parameter index
Parameter name
Default setting
Parameter number
9.5.2.1
T33 mode
[1] Voltage Mode
619
9.5.2.2
T33 High Voltage
10V
611
9.5.2.3
T33 Low Voltage
0.07 V
610
9.5.2.6
T33 High Ref./Feedb.
Value
50
615
AI1 - T33
9.5.2.7
T33 Low Ref./Feedb.
Value
0
614
9.5.3.1
T34 mode
[0] Current Mode
629
9.5.3.4
T34 High Current
20.00 mA
623
9.5.3.5
T34 Low Current
4.00 mA
622
9.5.3.6
T34 High Ref./Feedb.
Value
50. If
[1] North Amer-
ica
is selected for
P 1.2.1 Regional
Settings
, the default
value is 60.
625
AI2 - T34
9.5.3.7
T34 Low Ref./Feedb.
Value
0
624
9.5.1.1
T31 Mode
[0] 0-20mA
690
AO1 - T42
9.5.1.2
T31 Analog Output
[100] Output Fre-
quency
691
Relay
9.4.3.1
Function Relay
[9] Fault
540
5.12.4.1
Feedback 1 Resource
[2] Analog Input 34
720
PID
5.12.5.7
PID Normal / Inverse
Control
[0] Normal
730
5.9.2
Jog Reference
5.0
311
Jog
5.9.1
Jog Ramp Time
3 s
380
5.5.3.5
Reference Function
[0] Sum
304
5.5.3.7
Reference 1 Source
[1] Analog Input 33
315
5.5.3.8
Reference 2 Source
[0] Function
316
External reference
5.5.3.9
Reference 3 Source
[0] Function
317
5.5.4
Configuring Multi-Speed Control Mode
Multi-speed control mode allows to use 2 digital inputs for 4 different speeds. By using 1 more digital input, 8 speeds are possible.
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
59