Application Guide | iC2-Micro Frequency Converters
P 9.4.3.2 Relay ON-Delay
Enter the delay of the relay cut-in time.
Default value:
0.01
Parameter type:
Range (0.00–600.00)
Parameter
number:
541
Unit:
s
Data type:
uint16
Access type:
Read/Write
Selected
event
Relay
output
Selected
event
Relay
output
P 9.4.3.2 Relay
ON-Delay
P 9.4.3.2 Relay
ON-Delay
P 9.4.3.3 Relay
OFF-Delay
e3
0b
k1
37
.1
0
Figure 82: On Delay, Relay
P 9.4.3.3 Relay OFF-Delay
Enter the delay of the relay cut-out time. See
P 9.4.3.1 Function Relay
. If the selected-event condition changes before a delay timer
expires, the relay output is unaffected.
Default value:
0.01
Parameter type:
Range (0.00–600.00)
Parameter
number:
542
Unit:
s
Data type:
uint16
Access type:
Read/Write
Selected
event
Relay
output
e3
0b
k1
38
.1
0
P 9.4.3.2 Relay
ON-Delay
P 9.4.3.3 Relay
OFF-Delay
Figure 83: Off Delay, Relay
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
243