Application Guide | iC2-Micro Frequency Converters
Data type:
uint16
Access type:
Read/Write
P 2.7.5 Trip Delay at Current Limit
When the output current reaches the current limit (
P 2.7.1 Output Current Limit %
), a warning is triggered. If the current limit warning is
continuously present for the period specified in this parameter, the frequency converter trips. Enter 60 s = OFF to disable the feature.
Default value:
60
Parameter type:
Range (0–60)
Parameter
number:
1424
Unit:
s
Data type:
uint8
Access type:
Read/Write
7.4
Filters & Brake Chopper (Menu Index 3)
7.4.1
Status (Menu Index 3.1)
P 3.1.1 Brake Energy
View the brake power transmitted to an external brake resistor. The mean power is calculated on an average basis for the most recent
120 s.
Default value:
0
Parameter type:
Range (0.000–10000.000)
Parameter
number:
1633
Unit:
kW
Data type:
uint32
Access type:
Read
7.4.2
Brake Chopper (Menu Index 3.2)
P 3.2.1 Enable Brake Chopper
Select method for dissipation of excess brake energy.
Default value:
0 [Disable]
Parameter type:
Selection
Parameter
number:
215
Unit:
–
Data type:
enum
Access type:
Read/Write
Selection number
Selection name
0
Disable
1
Enable
P 3.2.2 Brake Chopper Voltage Reduce
This parameter can reduce the DC voltage where the brake resistor is active. It is only valid for T4 unit.
Default value:
Size Related
Parameter type:
Range (Size Related)
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
119