Application Guide | iC2-Micro Frequency Converters
NOTICE
Sleep mode is not active when local reference is active (set speed manually with navigation buttons on the control panel). Does
not work in Local mode. Remote setup in open loop must be carried out before setting input/output in closed loop.
P 5.12.7.1 Sleep Mode in Process Closed-loop Mode
This parameter is for sleep mode running in process closed loop. Use this parameter to set whether the feedback is detected for entering
sleep mode.
Default value:
0
Parameter type:
Selection
Parameter
number:
2202
Unit:
–
Data type:
enum
Access type:
Read/Write
Selection number
Selection name
Selection description
0
Feed. and Speed
Feedback is detected together with the speed.
1
Speed
Feedback is not detected, only sleep speed and time are
checked.
2
Feedback
Feedback is detected only.
P 5.12.7.2 Minimum Run Time
Set the minimum running time for the motor after a start command (digital input or bus) before entering the sleep mode.
Default value:
10
Parameter type:
Range (0–600)
Parameter
number:
2240
Unit:
s
Data type:
uint16
Access type:
Read/Write
P 5.12.7.3 Minimum Sleep Time
Set the minimum time for staying in sleep mode. This setting overrides any wake-up conditions.
Default value:
10
Parameter type:
Range (0–600)
Parameter
number:
2241
Unit:
s
Data type:
uint16
Access type:
Read/Write
P 5.12.7.4 Wake-Up Speed [Hz]
This parameter is used when
P 5.4.2 Operation Mode
is set for open loop, and the speed reference is from an external controller. Set the
reference speed when the Sleep Mode is deactivated.
Default value:
100
Parameter type:
Range (0–4000)
Parameter
number:
2243
Unit:
Hz
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |