Application Guide | iC2-Micro Frequency Converters
Default value:
0 [No function]
Parameter type:
Selection
Parameter
number:
722
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter:
Selection number
Selection name
0
No function
1
Analog Input 33
2
Analog Input 34
4
Frequency Input 18
P 5.12.4.3 Feedback 1 Conversion
Use this parameter to select a conversion for the Feedback 1 signal. To leave the feedback signal unchanged, select
[0] Linear
.
Default value:
0 [Linear]
Parameter type:
Selection
Parameter
number:
760
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter:
Selection number
Selection name
0
Linear
1
Square root
P 5.12.4.4 Feedback 2 Conversion
Use this parameter to select a conversion for the Feedback 2 signal. To leave the feedback signal unchanged, select
[0] Linear
.
Default value:
0 [Linear]
Parameter type:
Selection
Parameter
number:
762
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter:
Selection number
Selection name
0
Linear
1
Square root
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
179
Содержание iC2
Страница 1: ...iC2 Micro Frequency Converters Application Guide drives danfoss com...
Страница 2: ......
Страница 10: ...10 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 290: ...290 Danfoss A S 2024 03 AB413939445838en 000301 130R1254 Application Guide iC2 Micro Frequency Converters...
Страница 291: ......