Application Guide | iC2-Micro Frequency Converters
Data type:
uint16
Access type:
Read/Write
P 5.6.15 Sync. High Starting Torque Time [s]
Use this parameter to set the high starting torque time for a PM motor in VVC+ mode.
Default value:
Size Related
Parameter type:
Range (0.00–60.00)
Parameter
number:
3020
Unit:
s
Data type:
uint16
Access type:
Read/Write
P 5.6.16 Sync. High Starting Torque Current [%]
Use this parameter to set the high starting torque current for a PM Motor in VVC+ mode.
Default value:
Size Related
Parameter type:
Range (0.0–200.0)
Parameter
number:
3021
Unit:
%
Data type:
uint 32
Access type:
Read/Write
7.6.6
Stop Settings (Menu Index 5.7)
P 5.7.1 Function at Stop
Use this parameter to select the drive function after a stop command or after the speed is ramped down to the level set in
P 5.7.2 Min
Speed for Function at Stop [Hz]
.
Default value:
0 [Coast]
Parameter type:
Selection
Parameter
number:
180
Unit:
–
Data type:
enum
Access type:
Read/Write
The following are the selections for the parameter.
Selection number
Selection name
Selection description
0
Coast
Leaves the motor in free mode
1
DC Hold/Motor Preheat
Energizes the motor with a DC-hold current (see
P 5.7.6 DC Hold
Current %
).
Danfoss A/S © 2024.03 AB413939445838en-000301 / 130R1254 |
169